A gas pressure test is required after any gasfitting work, and a licensed gasfitter must carry it out with an approved test medium and a calibrated instrument. The installation must hold its pressure with no drop at all. If you smell gas or suspect a leak, treat it as an emergency, leave the building and call a licensed gasfitter straight away.
TL;DR:
- In New South Wales, the licensed gasfitter must lodge a compliance or inspection certificate within five business days after completing the work.
- Only air, nitrogen, carbon dioxide, or operating gas may be used; oxygen is prohibited because it can ignite violently around combustible materials.
- For low pressure tests, Western Australian guidance cites 2 kPa or 4 kPa for domestic bottled gas, but the applicable standard sets the required value.
- Any pressure loss means the installation must stay out of service until a licensed gasfitter repairs the leak and repeats the complete test.
- A pressure pass does not clear an appliance for use; extraction fans can cause carbon monoxide spillage, requiring separate negative pressure and spillage checks.
Table of Contents
- When is a gas pressure test required, and who must do it?
- Which test media and pressures are approved?
- What equipment is used for a gas tightness test?
- How is a gas pressure test performed, step by step?
- What does a pass or fail result mean?
- Why do gasfitters also test for negative pressure and carbon monoxide?
- Why should a licensed gasfitter perform and certify the test?
- What safety precautions and protective equipment apply during testing?
- What are the common causes of test failure, and how are they fixed?
- How should you keep gas test records beyond the certificate?
- When and how should you retest after a failed gas pressure test?
- What does an experienced gasfitter see go wrong most often?
- How can we help with gas testing, repairs and certification?
- FAQ
- Sources
When is a gas pressure test required, and who must do it?
Gas installations must be tested for tightness immediately after any gasfitting work, including installation, alteration, repair or extension. NSW Government compliance guidance says licensed gasfitters must perform these tests and submit a certificate of compliance or inspection within five business days of finishing the job.
Here is what that means in practice:
- Any new, altered, repaired or extended gas line needs a tightness test before it goes into service.
- The test procedure comes from AS/NZS 5601.1 Appendix E, read alongside state gasfitting regulations.
- The licensed gasfitter signs off the result, not the homeowner or property manager.
- Work is reported through the state compliance portal within the regulator’s timeframe.
- A failed installation or a found defect can lead to a defect notice, and Building and Energy in Western Australia notes that non-compliance can bring enforcement, including prosecution or suspension of a gasfitting authorisation.
Which test media and pressures are approved?
The rules on test media are strict. Regulation 26(2) of the Gas Standards (Gasfitting and Consumer Gas Installations) Regulations 1999%20Regulations%201999%20-%20%5B05-c0-01%5D.html?OpenElement=) lists the approved media and bans the rest.
- Permitted: air, nitrogen, carbon dioxide or the operating fuel gas.
- Prohibited: oxygen, which must never be used for pressure testing.
- Pressures: the test runs at operating pressure or a value set by the standard. For low nominal pressures, WA gas guidance describes testing to 2 kPa or 4 kPa for domestic LP gas installations.
- Hold times: many domestic installations require an appropriate hold time, while larger volumes need longer stabilisation and different hold times under the standard.
Test media rule: oxygen is strictly prohibited for gas pressure testing, and only air, nitrogen, carbon dioxide or the operating fuel gas may be used under regulation 26(2). Oxygen can ignite violently around oils and fuel gas, so there is no safe workaround.
What equipment is used for a gas tightness test?
A tightness test is a sensitive, low-pressure check. It is different from a strength test, which uses higher pressure to prove structural integrity. Using an insensitive gauge, or skipping the tightness test, risks leaving a latent leak behind.
Professionals typically work with:
- digital manometers and U-tube manometers
- low-pressure test kits
- pressure adaptors that match the appliance or meter outlet
- calibrated gauges with a resolution fine enough to show a small pressure change
Calibration matters because temperature swings can mimic a pressure drop. A calibrated, sensitive instrument, combined with proper stabilisation, separates a real leak from a false alarm.
Pro Tip: A manometer reads a pressure change, not a leak. Always allow the system to stabilise before you record the starting pressure, or temperature drift will fool you.
Consumer gauges and hardware-store kits rarely meet the sensitivity and calibration a compliant test demands. A full compliance test also needs a licence to certify it, so book a licensed gasfitter instead.

How is a gas pressure test performed, step by step?
WA’s gas tightness testing requirements follow AS/NZS 5601 Appendix E. A standards-aligned test runs in this order:
- Depressurise the installation and isolate the meter or cylinder.
- Disconnect or isolate appliances as the procedure requires.
- Seal all open fittings and outlets.
- Connect the calibrated test instrument with the correct adaptors.
- Pressurise to the specified test pressure with an approved medium.
- Isolate the pressure source so the test section is a closed system.
- Allow the pressure to stabilise for the period required by the applicable procedure.
- Record the starting pressure and observe for the full hold period required by the applicable procedure.
- Confirm there is no pressure drop. If there is, do not commission: locate the leak, repair it and retest.
Pro Tip: Write down the stabilisation time and the start and finish readings. Those three numbers are the heart of your test record.
What does a pass or fail result mean?
Interpretation is blunt. There is no allowable leakage rate for domestic gas systems, and any perceptible pressure drop is a fail.
- Pass: the pressure holds steady for the whole observation period, so the installation is gas-tight and can be commissioned, subject to appliance and ventilation checks.
- Fail: any pressure loss means the system must be isolated, repaired by a licensed gasfitter and retested.
- Paperwork: the licensed contractor documents the result and issues the certificate of compliance or inspection, then keeps records ready for audits.
A pass on pressure alone does not make an installation fully safe. Compliance also covers appliances, flues and ventilation under AS/NZS 5601.1, which is why the next section matters.
Why do gasfitters also test for negative pressure and carbon monoxide?
A gas-tight system can still be unsafe in use. Energy Safe Victoria’s GIS 38 explains that extraction fans can create negative pressure that pulls combustion products back into a room, causing carbon monoxide spillage even when the installation is otherwise gas-tight.
The check usually includes these steps:
- a baseline reading with the appliance running
- a negative-pressure smoke test with fans and vents operating
- a carbon monoxide spillage test
- an assessment of the results
If negative pressure is found, add ventilation or isolate the appliance. If spillage is detected, isolate the appliance and look for faults before it is used again. Energy Safe’s gasfitter toolkit also recommends documented reporting to clients after these checks.
Passing a tightness test does not remove the need for carbon monoxide spillage and negative-pressure checks. They answer a different safety question.
Why should a licensed gasfitter perform and certify the test?
In NSW, only licensed gasfitters can undertake repairs or renovations involving gas, and a certificate of compliance or inspection must follow the work.
- Licensed gasfitters carry out the pressure test, issue the certificate and report the work on time.
- AS/NZS 5601.1 and state regulations fix the procedure and the obligations.
- We offer gasfitting, so you can rely on our work for your plumbing needs.
What safety precautions and protective equipment apply during testing?
Gas testing is controlled work, and a gasfitter plans for the worst case before pressurising anything. The test medium itself can be hazardous, and so can the surroundings.
- Ventilation: work in a well-ventilated area, and open doors and windows in enclosed spaces. Nitrogen and carbon dioxide can displace breathable air.
- Ignition control: no naked flames, smoking, or sparking tools near the work. Switch off nearby ignition sources and warn other people on site.
- Isolation: confirm the supply is shut off and locked or tagged so nobody turns it back on mid-test.
- Protective equipment: safety glasses for fitting and disconnecting work, gloves for handling pipe and fittings, and sturdy footwear. A portable gas detector is sensible when working with fuel gas.
- Never use oxygen: it is banned for pressure testing, as covered above.
- Controlled pressurising: raise pressure gradually, watch the instrument and never exceed the specified test pressure.
- Leak detection fluid: use an approved leak detection solution on joints once the system is pressurised, and wipe it off after.
- Clear exit: know where to go if gas is smelled, and keep people out of the area.
If you smell gas, Energy Safe Victoria advises treating it as a life-threatening emergency: evacuate, shut off the gas supply if it is safe to do so, and call a licensed professional. Do not try to repair or retest it yourself. Our guide to safety steps during a gas leak covers the immediate actions in more detail.
What are the common causes of test failure, and how are they fixed?
Most failures trace back to a handful of causes, and a good gasfitter works through them in order rather than guessing.
- Loose or poorly made joints: threaded fittings and unions are the usual suspects. Recent audits flagged non-compliance in concealed screwed fittings, and NSW jointing requirements set out what is allowed for concealed piping.
- Unsealed outlets: a missed cap, plug or appliance connection looks exactly like a leak.
- Faulty appliance isolation: a leaking appliance valve or regulator inside the test section can bleed pressure.
- Damaged or corroded pipe: age, ground movement or physical damage can open a pinhole.
- Inadequate stabilisation: starting the clock too early lets temperature change look like pressure loss.
- Insensitive or uncalibrated instruments: a gauge that cannot resolve small changes hides real leaks, and drifting gauges invent fake ones.
- Temperature swings: a pipe in direct sun or near a heater changes pressure without any leak.
The fix is methodical. Isolate the installation into sections, apply approved leak detection fluid to joints, and test each section separately to narrow the location. Once found, remake or replace the joint or component, then retest from the beginning. If the leak is hidden inside a wall or slab, non-invasive leak detection can pinpoint it before anyone opens up the structure.
How should you keep gas test records beyond the certificate?
The certificate is the legal minimum. Good records protect you at sale, at audit and when something goes wrong later. A thorough file should include:
- the date, address and scope of the work tested
- the test medium, test pressure and hold time used
- the starting and finishing pressure readings and the stabilisation time
- the instrument used and its calibration date
- the pass or fail result and the gasfitter’s name and licence number
- notes on any defects found, repairs made and retests carried out
- any carbon monoxide and negative-pressure results, with appliance details
Keep these records together, for example in a single folder or digital file, and store a copy off-site. Property managers should link each record to the specific property and service date, so a history builds up over time. Lodge certificates through the relevant state portal within the required window, since NSW requires work to be reported within five business days.
Hand copies to the owner or tenant, and keep records for as long as the installation stays in service. They also help future tradespeople spot patterns, such as a joint that keeps failing or an appliance that needs attention.
When and how should you retest after a failed gas pressure test?
A failed test is a stop sign. The installation must not be commissioned, and appliances must stay off until it passes. The retest follows the repair, not the other way round.
- Isolate the supply and make the area safe.
- Find the leak using sectional testing and approved leak detection fluid.
- Repair or replace the faulty joint, pipe or component.
- Depressurise, reseal and reconnect the calibrated instrument.
- Restart the full procedure: pressurise, isolate, stabilise and observe for the whole hold period.
- Confirm no pressure drop, then document the result and issue the certificate.
Do not shorten the stabilisation or hold time because the repair “looks fine”. A retest is a complete test, not a quick check. If the system fails again, repeat the search, because there may be more than one leak. Repairs to gas installations must be done by a licensed gasfitter, and the result still needs a certificate within the regulator’s timeframe.
If you are weighing up a repair after a failed test, the defective gas installation requirements set out the testing and certificate obligations that apply.
What does an experienced gasfitter see go wrong most often?
Most disputed results come down to the same two things: rushing the stabilisation and trusting an uncalibrated gauge. Temperature drift can look exactly like a slow leak, and I would rather lose two extra minutes than chase a leak that is not there. A real smell of gas is different: that is an emergency call, not a booking. Keep every certificate and test record, because buyers, insurers and auditors do ask for them.
— Peter Honey
How can we help with gas testing, repairs and certification?
We offer gasfitting. Check our site for details about the services we provide. If you suspect a leak, our team is available 24/7 for emergencies.
When you call or book, have these ready:
- the property address and type (house, unit, commercial)
- whether the supply is mains gas or bottled gas
- what work was done, or what you have noticed
- the appliances connected

Book through our gas fitting service page or reach our emergency plumbers straight away. Our call out fee is $0, and we can give you upfront pricing before work starts.
FAQ
How many psi to pressure test a gas line?
Australian standards work in kilopascals, not psi. For low nominal pressures, guidance describes testing to 2 kPa or 4 kPa, depending on the installation, with the exact value set by AS/NZS 5601 Appendix E.
What are the rules for gas tightness tests?
Gas installations must be tested after any gasfitting work, and licensed gasfitters must issue a certificate of compliance or inspection within five business days. The test must show no pressure drop, since no leakage is allowed.
How do you use a manometer?
You connect it to the test point with the correct adaptor, pressurise the closed section, then let the reading stabilise before recording the starting pressure. You then watch it for the full hold period. For a compliance test, a licensed gasfitter should do this with a calibrated instrument.
What should I do if the gas pressure on my meter is low?
Do not try to adjust the meter or regulator yourself. Contact your gas retailer or a licensed gasfitter to check the supply and the installation. If you smell gas, leave the building and call for emergency help.
Sources
- Gasfitter compliance and regulatory obligations | NSW Government
- GIS 38: Testing for negative pressure and carbon monoxide spillage | Energy Safe Victoria